Forward
Printable cheat sheet

Hit ⌘ + P. Designed to print to 8.5×11 portrait; folds in half for the pocket.

Forward · field cheat sheet

NEC quick reference

Ampacity, voltage-drop K, breaker pairing, conduit fill. Sanity-check only — verify with the engineer of record.

Table 310.16 — copper ampacity (most common temps)

Size60°C75°C90°C
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
350 kcmil260310350
500 kcmil320380430

Reminder: NEC 110.14(C) terminations limit the effective column. ≤100 A circuits use 60°C; >100 A use 75°C — even if your insulation is 90°C-rated.

Voltage drop K-factors (75°C)

  • Copper: K = 12.9
  • Aluminum: K = 21.2

VD (single-phase) = 2·K·I·L / cmils; VD (three-phase) = √3·K·I·L / cmils.
NEC informational: 3% branch / 5% total.

Common breaker / wire pairings

BreakerCu (75°C)Al (75°C)
15 A14 AWG
20 A12 AWG10 AWG
30 A10 AWG8 AWG
40 A8 AWG6 AWG
50 A6 AWG4 AWG
60 A6 AWG4 AWG
100 A3 AWG1 AWG
125 A2 AWG1/0 AWG
150 A1/0 AWG3/0 AWG
200 A2/0 AWG4/0 AWG
400 A500 kcmil750 kcmil

Conduit fill — 40% max for ≥3 conductors (NEC 300)

  • 1 conductor max: 53% fill
  • 2 conductors max: 31%
  • ≥3 conductors max: 40%