HVAC quick reference (IMC + ASHRAE)

CFM ↔ BTU/h

Sensible heat: BTU/h = 1.08 × CFM × ΔT. Solve for CFM: CFM = BTU/h ÷ (1.08 × ΔT). Common ΔT: 18-22°F cooling, 60-80°F heating.

Duct friction-loss targets

  • Low-velocity (commercial): 0.08 in WC / 100 ft
  • Medium-velocity: 0.10-0.15 in WC / 100 ft
  • High-velocity (VAV runs): 0.20+ in WC / 100 ft

ΔP/L = 0.109 × Q^1.9 / D^5.02 (round-duct approximation).

ASHRAE 62.1 ventilation rates

OccupancyRp (CFM/person)Ra (CFM/sf)
Office50.06
Conference room50.06
Classroom (K-12)100.12
Lecture hall7.50.06
Retail sales7.50.12
Restaurant dining7.50.18
Healthcare exam100.18
Lobby / corridor50.06

HVAC load rules of thumb

  • Cooling BTU/SF: sun-heavy 32, average 25, shaded 20
  • Climate-zone multiplier: zone 1 = 1.15, zone 4 = 1.0, zone 8 = 0.80
  • Heating BTU/SF: 20 (zone 1) to 55 (zone 8)
  • Tons cooling = BTU/h ÷ 12,000
  • 1 ton ≈ 400 CFM